Electrical Products & Services
Measure distortion first, then select reactors, filters, multipulse or AFE solutions and verify PCC compliance across operating loads.

To reduce VFD harmonics, I start with measurements – not a filter purchase. On Canada’s 60 Hz supply, six-pulse drives commonly produce 5th (300 Hz) and 7th (420 Hz) harmonics. The right fix depends on your loads, supply and readings.
Here’s the approach I follow:
Lower drive-current distortion alone doesn’t prove the job is done. I use <u>verified PCC results</u> to judge whether the system meets its requirements.

How to Reduce VFD Harmonics: 4 Steps
Update the one-line diagram to pinpoint harmonic sources. Trace the supply from the utility connection through the transformer, panels and feeders to each VFD load. Include other nonlinear loads on that supply: UPS units, battery chargers, EV chargers and LED drivers. Mark each capacitor bank’s kVAR, switching method and location. These banks can create resonance with system impedance.
For each drive, record its manufacturer, model, voltage, phase, input current and rating in kW or horsepower. Check the documentation for its rectifier type – six-pulse, 12-pulse or active front end – and any installed AC line reactor, DC-link choke or harmonic filter. Record regenerative operation, motor rating, cable length and whether multiple drives share a common DC bus. Do not infer rectifier type from power rating.
Next, classify how each load runs and when it peaks.
Fans and centrifugal pumps are usually variable-torque loads; conveyors and positive-displacement pumps are usually constant-torque loads. Loading patterns affect harmonic output, so record minimum, normal and maximum speed, operating current, start/stop events, and daily or seasonal schedules. Note which drives run together rather than simply adding their nameplate ratings. Use this operating profile to decide what to measure next.
Have qualified personnel verify transformer kVA, percent impedance, feeder details, available fault current and demand current. Then compare expected input kVA – including other nonlinear loads – with transformer capacity, not motor kW alone. This helps assess whether distortion is source-limited or load-driven. Record standby-generator operation separately: changes in source impedance can alter distortion even when the loads stay the same.
If drives account for only a small share of demand, start by checking supply voltage, connections and impedance. Request a harmonic study when drive loading is high, several large drives run together, capacitor banks are present or source conditions are uncertain. Use the diagram, equipment inventory and operating schedule to guide the measurement stage.
Use the load map from Step 1 to guide testing by a qualified electrical professional. They should use a properly rated power-quality analyser with matching voltage leads and current probes. For any energized work, follow the site’s electrical safety program, including PPE and arc-flash controls. Before logging, set the correct wiring configuration, nominal voltage and frequency, then verify probe direction and phase matching.
Start at the point of common coupling (PCC). Confirm its location with the utility or facility owner, and measure only where access is safe and permitted. Next, measure at VFD inputs and distribution panels under matching operating conditions. Distortion on one feeder suggests a local source. Similar voltage distortion at several locations suggests an upstream source or shared impedance.
Log long enough to cover minimum, normal and maximum simultaneous loads, including regular acceleration, deceleration and regeneration where supported. Record which equipment is running, drive speed, load and capacitor-bank switching alongside voltage THD, current THD, TDD, RMS current, true and displacement power factor, and waveforms.
For six-pulse drives, inspect the fifth, seventh, eleventh and thirteenth harmonics. Also check voltage imbalance and, on four-wire circuits, neutral current.
Base TDD on the established demand current, not a spot reading. At light load, current THD can look high because the fundamental current is small. Check harmonic amperes and loading before treating that percentage as a problem.
Compare the results with utility requirements, equipment specifications and IEEE 519 at the PCC, not at each VFD input. Limits depend on supply voltage, system strength and demand current. A universal “5% THD” target isn’t enough.
Use the required averaging intervals and statistical method rather than a single screen reading. Save time-stamped records of measurement locations, loads, analyser and probe details, settings, harmonic spectra and waveform files. These records form the baseline for post-change testing.
Use the worst-case readings to choose the mitigation method in Step 3.
Use the worst-case readings from Step 2 to select mitigation that meets PCC limits across the operating range – not just the drive size. Provide the recorded supply and load data, plus regenerative duty, available space, ventilation, ambient temperature and expansion plans.
Ask for harmonic performance data that matches the actual load profile.
| Solution | Best-fit application | Main benefit | Key limitation | Design checks |
|---|---|---|---|---|
| AC line reactor | Individual drives with moderate distortion | Reduces input distortion and supply-transient stress | Limited harmonic reduction | Typically 3–5% impedance; check current rating, voltage drop, heat and protection |
| DC-link choke | Individual drives with compatible choke provisions | Smooths DC-bus current and reduces input distortion | May not be enough on its own | Confirm compatibility, any existing choke and thermal limits |
| Passive harmonic filter | Stable loads with predictable harmonics | Reduces specific harmonic orders | Fixed tuning; resonance risk | Check impedance, capacitor banks, generator supply and minimum load |
| Active harmonic filter | Multiple drives with changing loads | Tracks changing harmonic loads | Added cost and cooling needs | Check compensation current, CT placement and polarity, response and fault rating |
| Multipulse drive | Larger, steady-duty loads | Cancels selected harmonics | Requires phase-shifting transformers; adds space and losses | Verify phase shifts, impedance, load balance and bypass operation |
| Active-front-end drive | New or replacement drives with low-distortion and regenerative duty | Shapes input current and returns braking energy | Low published input THD does not guarantee PCC compliance | Check load range, supply impedance, other loads and cooling |
Check the predicted PCC result for the full installation. Reducing distortion at one drive may still leave total distortion above the limit.
After selecting the device, check wiring, protection, cooling and bypass behaviour before installation.
Input harmonic mitigation is not the same as motor-side filtering. Output reactors, dv/dt filters and sine-wave filters address motor-terminal stress – not supply-current distortion.
Power-factor correction capacitors are not harmonic filters. Before combining them with mitigation equipment, check resonance and light-load behaviour.
Coordinate conductor sizing, disconnects, protective devices, grounding, equipment short-circuit ratings, ventilation and manufacturer instructions. Check whether bypass operation leaves any loads unfiltered, and whether generator or transfer-switch operation changes filter suitability.
Have qualified electrical personnel isolate all sources, apply lockout/tagout, observe DC-bus and capacitor discharge times, and verify absence of voltage. Follow the Ontario Electrical Safety Code and complete the required Electrical Safety Authority notification and inspection.
After installation, confirm that the mitigation works across the same operating range used for the baseline test.
Repeat the baseline test at the same PCC, panel, feeder and drive-input points. Use the same analyser setup and load bands, and record which drives and other nonlinear loads were running. A single spot reading can miss problems that appear as loads change.
Under those same conditions, compare post-change readings against the baseline and the project, utility and IEEE 519 limits used in Step 2. Check voltage THD, current THD, TDD at the PCC, individual harmonics – especially the 5th, 7th, 11th and 13th – RMS voltage and current, and true and displacement power factor. Include neutral current where relevant.
After warm-up under comparable loads, compare temperatures in °C against baseline readings and manufacturer ratings. Check spectra, alarms and fault logs for resonance, voltage distortion, heating, voltage drop and nuisance trips. Confirm that torque, noise and control performance have not worsened. Lower current THD alone does not confirm compliance.
Keep baseline and post-mitigation reports, analyser files, waveform and spectrum exports, timestamps, operating loads and supply-source status. Include equipment ratings, drive and filter model numbers, settings, protection settings and maintenance recommendations.
Set inspection intervals based on manufacturer instructions and how critical the loads are. Check cooling fans, ventilation, capacitor condition, connections and alarm logs. Use these records to schedule the next inspection and flag future changes that could alter harmonics.
Re-test after major load or supply changes, including new drives, transformer changes, capacitor-bank additions, filter replacement or recurring trips. Test generator operation separately where applicable. If readings still fall short of requirements, arrange a power-quality review before adding more mitigation.
For Ottawa Valley troubleshooting, maintenance and installation support, contact Draper Electric.
Follow a clear sequence: identify, measure, mitigate, and verify. Choose harmonic mitigation based on measured conditions, not symptoms. Use the load map, baseline harmonic readings, and PCC results to select compatible mitigation.
Check performance at the drive input, affected distribution points, and the PCC. PCC limits apply at the system level, not at each drive terminal.
Acceptance covers only the tested system. Reassess after changes to the load mix, supply capacity, or operating pattern.
Watch for signs of electrical instability: frequent circuit breaker trips, buzzing sounds, flickering or dimming lights, and warm or discoloured outlets. Unusual noises from electrical panels or equipment may also point to power quality issues.
These signs don’t prove that harmonics are causing your VFD trips. Contact a licensed electrician to inspect the system and confirm the cause.
Harmonic mitigation is worth the cost when measurable distortion puts performance or reliability at risk, or when reducing harmonics can help prevent costly equipment damage and downtime.
Compare the installed cost with the likely cost of repairs, replacement and business interruption if the problem persists. Before investing, Draper Electric recommends getting an itemized quote and having a professional assess the electrical system.
Yes, adding a standby generator can affect your existing harmonic mitigation and surge protection equipment. A licensed technician should check panel compatibility, grounding and bonding so these devices work as intended when switching between utility and generator power.
Draper Electric checks that these systems work together correctly, so your backup power doesn’t introduce new vulnerabilities or performance issues.